• EvacPro
  • EvacPro - Evacuation Alert Panel
  • EvacPro - Evacuation Alert Panel

EvacPro - Evacuation Alert Panel

Part No. Various
  • Complies with standard BS 8629:2019
  • Available in 16,32 or 48 zones variant
  • Protec 6000PLUS protocol
  • Vandal-proof enclosure
  • Printable toggle switch label (slide-insert)
  • 1 Amp loop alarm load capability

Product Details

EvacPro is the product name for the Protec Evacuation Alert Control and Indicating Equipment (EACIE) which is designed and manufactured to meet the recommendations of BS 8629:2019. This is required for use by Fire and Rescue Services to have the facility evacuate a high-rise accommodation building in an emergency.

The control panel is to be housed in a high-security tamper-proof vandal-resistant STS 205 BR2 enclosure, fitted with a patented BS EN 1303 lock as required by BS8629. This enclosure is to be provided by others. Each EvacPro control panel is of a modular design, supporting four digital addressable data loops with up to 100 addresses per loop and 16, 32 or 48 zone toggle switches.

Multiple EvacPro panels may be connected to further expand the system to create a building-wide evacuation system across large or complex sites.

The slide-in toggle switch labels ensures quick and clear identification of the Evacuation Zones, alongside red and yellow LED’s to show the activation status of the system.

Using the Protec 6000PLUS protocol enables addressable loop output devices such as 6000PLUS sounders and visual alarm devices (compliant with EN54 pt.23) to be added to the system.

The system is onsite programmable via a standard USB port with the Protec virtual panel software for commissioning and maintenance.

EvacPro Evacuation Alert Panel Specifications:

Environment 0°C to 40°C (95% RH no condensation or icing)
IP Rating IP30
Standby Load 0.24A (EvacPro/16) 0.26A (EvacPro/32) 0.28A (EvacPro/48)
Number of Loops 4
Total Loop Load 1A average, 2A peak, per loop
Charger Suitable external charger compliant with EN54-4
Standby Duration 72 hours dependant on loop loading and battery configuration
Auxiliary Fault Outputs 1 – Volt free changeover contacts rated at a maximum of 1A 24V dc
Relevant Standards BS 8629:2019* & EN54 Part 4

*When installed in STS 205 BR2 enclosure

 

STS 205 BR2 Enclosure Specification:

Construction STS 205 BR2 with BS EN 1303 lock
Mounting Position Wall mounted
Mounting Method Surface Mount
Outer Enclosure Colour RAL9006 Silver

 

Weights:

Weight of EvacPro Panel 9kg
Weight of GERDA Enclosure 69kg*

*Due to the weight of this enclosure, this needs to be mounted on a solid constructed wall.