• 3500-Panel
  • 3502 2 Zone Conventional Fire Alarm Control Panel

3502 2 Zone Conventional Fire Alarm Control Panel

Part No. 62-807-UK
  • Available in 2, 4 and 8 zone models
  • Attractive surface or recessed mounting
  • Comprehensive range of engineering functions
  • Zone disablements
  • Ability to differentiate between Manual Call Point or automatic detector alarm
  • Programmable sounders for automatic and/or manual activation 72 Hour standby as standard
  • Third party approved to latest EN54 Parts 2 and 4. Meets the requirements of BS5839 Part 1: 2013

Product Details

The Protec 3500 range of conventional control panels has been designed to provide a simple, user-friendly, highly cost effective option with inbuilt flexibility previously only found in more complex addressable systems.

With 2 detection zones the 3502 Fire Alarm control panel is ideal for small sized buildings such as industrial units, retail units, shops and schools.

The panel can be either surface or recessed mounted, with the controls and indications protected from unauthorised access by entering a user access code. These panel has the ability to identify if a ‘FIRE’ signal has been generated manually by a person activating a Manual Call Point (MCP) or automatically from a detector. This knowledge enables an appropriate cause and effect sequence to be implemented (time delays, for example) to allow for alarm verification for automatic detectors, but immediate alarms from MCPs. Cause and effect functions include coincidence detection, zone delays, pulsing sounders and fire relay. Interconnection with other systems is simplified as zones can be configured as ‘non-latching’, and there is a dedicated ‘class change input’ terminal. The 3502 control panel are third party approved to the latest European standard and meets all the requirements of BS5839 pt1.

Power Supply Mains 100V-240V ac
Integral Charger 600mA
Auxiliary 24V output 24V dc, 150mA max
Maximum Battery Size 2 x 12V 3.3Ah
Mains Fuse 16A time delay (not replaceable)
Battery Fuse 1.6A resettable fuse
Working Voltage 18V to 30V DC
Current Consumption 22mA (24V DC) + Zone Load
Number of Detector Zones 2
Max Zone Cable Length 500 metres
Max Zone Cable Capacitance 0.25µF
Max Zone Cable Resistance 15Ω per conductor
Detector Circuit EOL Values Resistive(8.2Ω) or capacitive (100µF+22Ω)
Max Quiescent Zone Load 5mA per zone
Max Number of Detectors 25 per zone (smoke or heat)
Maximum Number of Devices 32 (MCP and Dets) per zone
MCP Series Resistor Values 180Ω ±5%
Number of Alarm Circuits 2
Alarm Circuits EOL Value 10kΩ ±5% ¼W
Maximum Alarm Load 400mA per circuit
Class Change Input Activates alarm outputs
Global Fault Contacts 24V DC 1 A rating
Global Fire Contacts 24V DC 1 A rating
Temperature Range -5 to 40°C
Humidity Limit 95% Non-Condensing
Dimensions (mm) 228(W) x 345(H) x 111(D)

Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.

Contact our sales team today
Product
Acceptance *
Marketing