• TCF-142 Series - RS485 to Fibre Converters

TCF-142 Series - RS485 to Fibre Converters

Part No. Various
  • Ring and point-to-point transmission
  • Protects against electrical interference and chemical corrosion
  • Automatic Baud Rate Detection
  • Low Current
  • Wide Temperature Range
  • Single Mode and Multi Mode Fibre Compatible

Product Details

The Protec fibre converters are used to convert the RS485 signalling used when networking equipment, to optical fibre signals. Two variants of the interface are available, one that is compatible with multimode optical fibre and one that is compatible with single mode fibre. The correct unit must be specified for the fibre being used in a particular installation.

The units automatically detect the Baud rate being used on the system, meaning that, in general, no setup is required.

The interface is compatible with Protec 6500 fire alarm control equipment and also Cirrus HYBRID, Cirrus CCD, Pro Point Plus and Cirrus RDP range of devices.

Order Codes
TCF-142-M-ST – Multi-mode ST Connector
TCF-142-S-ST – Single-mode ST Connector

Serial Signals

RS-485-4w Tx+, Tx-, Rx+, Rx-, GND

Power Parameters

No. of Power Inputs 1
Input Current 15mA @ 24 VDC
Input Voltage 12 to 48 VDC
Overload Current Protection Supported
Power Connector Terminal block
Power Consumption 15mA @ 24 VDC

 

Physical Characteristics

IP Rating IP30
Housing Metal
Dimensions (with ears) (W)90 x (H)100 x (D)22 mm
Dimensions (without ears) (W)67 x (H)100 x (D)22 mm
Weight 320g
Installation Wall mounting

 

Environmental Limits

Operating Temperature -40 to 75°C (-40 to 167°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity 5 to 95% (non-condensing)

 

Serial Interface

Optical Fibre

TCF-142-M-ST Series: 100BaseFX ports (multi-mode ST connector)
TCF-142-S-ST Series: 100BaseFX ports (single-mode ST connector)
Low-Speed Fibre Module Multi-Mode Single-Mode
Fibre Cable Requirements 50/125 μm, 800 MHz G.652
62.5/125 μm, 500 MHz
Typical Distance 5 Km 40 Km
Wavelength Typical (nm) 850 1310
TX Range (nm) 840 to 860 1290 to 1330
RX Range (nm) 800 to 900 1100 to 1650
Optical

Power

TX Range (dBm) 0 to -5 0 to -5
RX Range (dBm) 0 to -20 0 to -25
Link Budget (dB) 15 20
Dispersion Penalty (dB) 1 1
Note: When using a power meter to measure the fibre TX power, set the baudrate to 9,600 bps and send data (00, …, 0h) to the serial converter’s serial port.
Pull High/Low Resistor for RS-485 150 kΩ (¼W ± 5%)
Terminator for RS-485 120Ω (¼W ± 5%)

Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.