• 6000-2LPZA
  • 2 Channel Loop Powered Zone Alarm Interface

2 Channel Loop Powered Zone Alarm Interface

Part No. 6000/2LPZA
  • 2 x Monitored Detection Zones
  • 2 x Monitored Alarm Outputs
  • Loop Powered
  • DIN Rail Mounted
  • Integral Short Circuit Isolator
  • Protec Algo-Tec 6000 Protocol

Product Details

The Protec 2 way loop zone alarm interface is a loop powered input / output device providing 2 local zones of conventional detectors and 2 local monitored alarm outputs.

Loop protocol Protec Algo-tec™ 6000 MX1
Loop isolator fitted Yes, on board (consult Protec DEL2110 for details)
Loop voltage range 18 to 28V peak loop
Number of loop addresses used 2 maximum, user and build configurable
24V Auxiliary input voltage range 18 to 28V dc
Environmental operational limits -10 to 50ºC (maximum 95% RH no condensation or icing)
Loop quiescent current (24V loop peak) 1.6mA + zone end of line current + zone loading
Loop alarm current (average) 18mA
Zone short circuit current (24V) 26mA peak ± 2mA
Zone end of line requirements (I/P 1 & I/P 2) Resistive – 8.2k ±5% ¼W, Capacitive – 100μ F ±20% in series with 22Ω ±5% ¼W
Input cabling requirements Maximum cable resistance 6Ω per conductor
Maximum cable capacitance 0.2μ F between cable conductors
Monitored input end of line details End of line resistor value 47kΩ 1/4W ±5%
Monitored input short circuit threshold Below 230Ω
Monitored input fire threshold Below 7.85kΩ
Monitored input pre-alarm threshold Below 32kΩ ( Input 3 only )
Monitored input open circuit threshold Above 111kΩ
Clean contact output details Single pole changeover rated for 8A maximum at 30V DC non inductive
Weight 245g ( including din rail housing, no backbox, 4 way build )
LED Indicator Use only high brightness LED (Protec stock code: NK 02-676-46)

Technical documents such as Manuals, Software downloads, BIM families, and more are available via our Client / Support Portal. To access, please Sign up or Login to your account.

Contact our sales team today
Product
Acceptance *