• 6000-4IO
  • 4 Channel Input/Output Interface

4 Channel Input/Output Interface

Part No. 6000/4IO
  • 2 x Monitored Detection Zones
  • 2 x Monitored Inputs
  • 2 x Monitored Alarm Outputs
  • 2 x Volt Free Changeover Contacts
  • Auxiliary 24vDC Powered
  • DIN Rail Mounted
  • Integral Short Circuit Isolator
  • Protec Algo-Tec 6000 Protocol

Product Details

The Protec 4 way input/output interface is a auxiliary powered input / output device providing 2 local zones of conventional detectors, 2 monitored inputs, 2 local monitored alarm outputs and two volt free changeover contacts. The contacts may be used to connect to ancillary equipment.

Loop protocol Protec Algo-tec™ 6000 MX1
Loop isolator fitted Yes, on board (consult Protec DEL2110 for details)
Loop voltage range 18 to 28V peak loop
Number of loop addresses used 4 maximum, user and build configurable
24V Auxiliary input voltage range 18 to 28V dc
Environmental operational limits -10 to 50ºC (maximum 95% RH no condensation or icing)
Loop quiescent current (24V loop peak) 0.6mA
Loop alarm current (average) 0.6mA
Zone short circuit current (24V) 26mA peak ± 2mA
Zone end of line requirements (I/P 1 & I/P 2) Resistive – 8.2k ±5% ¼W, Capacitive – 100μ F ±20% in series with 22Ω ±5% ¼W
Input cabling requirements Maximum cable resistance 6Ω per conductor
Maximum cable capacitance 0.2μ F between cable conductors
Zone quiescent current 500μ A maximum ( 10 Protec 3000 detectors per zone )
Zone reset time 2 seconds, with active zone discharge
Manual Call Point requirements Must be fitted with a series 330Ω or 180Ω resistor
Zone short circuit threshold Below 5% of supply voltage
Zone fire threshold Below 70% of supply voltage
Zone resistive open circuit threshold Above 92% of supply voltage
Monitored input end of line details End of line resistor value 47kΩ 1/4W ±5%
Monitored input short circuit threshold Below 230Ω
Monitored input fire threshold Below 7.85kΩ
Monitored input pre-alarm threshold Below 32kΩ ( Input 3 only )
Monitored input open circuit threshold Above 111kΩ
Sounders supported Protec 3000 series
Sounder circuit end of line 10kΩ ¼W ±5%
Sounder circuit cable requirements Maximum cable resistance depends on Volt drop calculations
Maximum cable capacitance 0.1 F between cable conductors.
Sounder short circuit fault threshold Below 2kΩ
Sounder open circuit fault threshold Above 18kΩ
Sounder current limit (maximum) 1.6A
Sounder circuit fuses 20mm x 5mm 1.6A Quick Blow
Clean contact output details 1 Single pole changeover rated for 8A maximum at 30V DC non inductive
Weight 245g ( including din rail housing, no backbox, 4 way build )
LED Indicator Use only high brightness LED (Protec stock code: NK 02-676-46)